Анотація

Reasons of failures of voltage on busbar a feed-in port cranes «Sokol», at imposition of work of mechanisms of getting up of a few cranes are exposed. It is set that by principal reason of such failures exceeding the requirements of standard of quality of electric power, is inductive resistance of phases of busbar. Application of cables in a crane network substantially promotes its carrying capacity, which allows at the end of moorage to set the electrohydraulic crane of the LIEBHERR firm, possessing higher carrying capacity and boom.

Опис

Ключові слова

трансформатор, мощность, напряжение, электроэнергия, сопротивление, эффект поверхностный, эффект близости, моделирование математическое

Бібліографічний опис

Радимов С. Н. Повышение пропускной способности кранового шинопровода морского порта / С. Н. Радимов, В. Л. Беляев, А. В. Ковченко // Вестник Нац. техн. ун-та "ХПИ" : сб. науч. тр. Темат. вып. : Проблемы автоматизированного электропривода. Теория и практика. – Харьков : НТУ "ХПИ", 2010. – № 28. – С. 349-350.