    Case study of incorrectly used current harmonics mitigation system
    (NTU "KhPI", 2017) Volkov, I. V.; Podolnyi, S. V.
    The paper describe a real case of a failed power transformer due to incorrectly applied active current harmonics mitigation system (active filter) for VFD drives. The used mitigation system injected high frequency current spectrum into the power system what led to overheating in the system components mainly due to skin effect. The possibility of such a problem should always be taken into account when choosing a specific scheme of the active filter.